LMTD Calculator – Log Mean Temperature Difference for Heat Exchangers

Use this free LMTD Calculator to find the log mean temperature difference of a heat exchanger in parallel-flow or counter-flow mode. Enter the hot and cold inlet and outlet temperatures — and optionally the overall coefficient U and area A to also get the heat transfer rate Q = UA·LMTD.

HOT in out heat exchanger COLD out in counter-flow: streams run opposite ways

Formula

LMTD = (ΔT₁ − ΔT₂) / ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the temperature differences between the hot and cold streams at the two ends of the exchanger. For parallel flow: ΔT₁ = Th1 − Tc1 and ΔT₂ = Th2 − Tc2. For counter-flow: ΔT₁ = Th1 − Tc2 and ΔT₂ = Th2 − Tc1. The heat transfer rate is then Q = U × A × LMTD. If ΔT₁ = ΔT₂, the LMTD is simply that common value.

How to use

Worked example

A counter-flow exchanger: hot fluid enters at 90 °C and leaves at 60 °C; cold fluid enters at 20 °C and leaves at 40 °C.
ΔT₁ = 90 − 40 = 50 K · ΔT₂ = 60 − 20 = 40 K
LMTD = (50 − 40) / ln(50/40) = 10 / 0.2231 = 44.81 K
With U = 500 W/m²·K and A = 2 m²: Q = 500 × 2 × 44.81 = 44,814.2 W ≈ 44.81 kW.

FAQ

Why not just use the average of ΔT₁ and ΔT₂?
The temperature difference changes along the exchanger in a logarithmic way, not a straight line. The plain average (45 K here) is close in this example but can be far off when ΔT₁ and ΔT₂ differ a lot — the log mean is the correct average driving force.

Why is counter-flow usually better?
In counter-flow the temperature difference stays more even along the whole exchanger, giving a larger LMTD for the same four temperatures (44.81 K here versus 39.91 K in parallel flow) — and the cold stream can even leave hotter than the hot stream's outlet, which parallel flow can never do.

What is a "temperature cross"?
It means the temperatures you entered are physically impossible for that flow arrangement — one of the end differences comes out zero or negative, so no real exchanger could produce them. Check the inlet/outlet values.