Phase Angle Calculator – φ = tan⁻¹((XL − XC)/R), Leading or Lagging
Use this free Phase Angle Calculator to find the angle φ between voltage and current in a series RLC circuit. Enter R, L, C and the frequency — the sign of the angle tells you at a glance whether the load is inductive (current lags) or capacitive (current leads).
Formula
φ = tan−1( (XL − XC) / R ), with XL = 2πfL and XC = 1/(2πfC). A positive φ means the voltage leads the current (inductive); a negative φ means the current leads the voltage (capacitive).
How to use
- Enter R in ohms, then L and C with their units.
- Enter the supply frequency in hertz.
- Click "Calculate" for XL, XC, the phase angle in degrees, and whether the current leads or lags.
Worked example
A series circuit has R = 100 Ω, L = 2 H and C = 10 µF at f = 50 Hz.
XL = 2π × 50 × 2 = 628.32 Ω and XC = 1 / (2π × 50 × 10 × 10−6) = 318.31 Ω.
φ = tan−1( (628.32 − 318.31) / 100 ) = tan−1(3.10) = +72.12°.
The angle is positive and large: the load is strongly inductive and the current lags the voltage by 72.12°.
FAQ
What does "lagging" and "leading" mean?
It describes which waveform reaches its peak first. In an inductive load the current wave is delayed — it lags behind the voltage. In a capacitive load the current peaks first — it leads. Power factor labels like "0.8 lagging" come straight from this angle.
When is the phase angle zero?
At resonance, where XL = XC. Voltage and current are then perfectly in step, the power factor is 1, and all the supplied power does useful work.
How is φ related to the power factor?
The power factor is simply cos φ. A 72.12° angle gives cos φ ≈ 0.31 — a poor power factor — while φ near 0° gives a power factor near 1, which is what supply companies want.