Voltage Drop Calculator – Cable Voltage Drop 2ρLI/A
Use this free Voltage Drop Calculator to find how much voltage is lost along a cable run. Enter the cable length, the current and the wire size — the calculator counts both the go and return wires, as in a real circuit.
Formula
Vdrop = 2 × ρ × L × I ÷ A
The factor 2 covers the go and return wires. Each wire has resistance R = ρL/A, so the loop resistance is 2ρL/A and the drop is I × that resistance.
How to use
- Pick the cable material (copper or aluminium) — or choose "Custom" and type ρ.
- Enter the one-way cable length, the current, and the wire area in mm².
- Optionally add the supply voltage to see the percentage drop and the voltage left at the load. Click "Calculate".
Worked example
A copper cable runs 20 m to a load drawing 10 A. The wire area is 2.5 mm² and the supply is 230 V.
Vdrop = 2 × 1.68 × 10⁻⁸ × 20 × 10 ÷ (2.5 × 10⁻⁶) = 2.688 V.
That is 2.688 ÷ 230 = 1.169% of the supply, leaving 230 − 2.688 = 227.312 V at the load.
FAQ
How much voltage drop is acceptable?
Wiring rules of thumb suggest keeping the drop under about 3% for lighting and 5% overall in an installation. Too much drop makes lamps dim, motors weak and electronics unreliable.
How can I reduce the voltage drop?
Use a thicker cable (bigger mm²), shorten the run, or reduce the current. Doubling the wire area halves the drop, because resistance falls as area rises.
Why is the factor 2 in the formula?
Current must travel to the load and back, so it passes through two lengths of cable. Each one drops voltage, and the load loses the sum of both drops.